Commissioning FL5000 as an NTP Time Server

Timing guide Published

Check the FL5000 reference source, then use client offset, delay and source status to verify NTP synchronization.

A shared time reference helps engineers compare event logs across servers, switches and voice systems. The FL5000 supports NTP for standard network clients and PTP for equipment that requires precision timing. Use a representative client to confirm performance at the endpoint.

Establish the reference and verify the client

  1. Check the active reference and synchronization state from the FL5000 management interface. Record the installed oscillator option and the expected behaviour when the reference is lost.
  2. Configure an NTP client to use the equipment's assigned service address. Verify reachability, the selected peer, offset and round-trip delay over several polling intervals.
  3. Check a client from each relevant network segment. A client can reach the server while an asymmetric path still introduces timing error.

Test recovery before acceptance

In an agreed maintenance window, interrupt the primary reference and record the server's status, the client's observed offset and the recovery time. If PTP also runs on the unit, record it separately from the NTP result. Use the FL5000 datasheet to confirm the interfaces and oscillator configuration.

Technical reference

IETF RFC 5905: NTPv4 protocol and clock measurements